BS 476 Part 22 Fire Resistance
作者:admin    发布于:2022-02-16 10:37:34    文字:【】【】【

Fire tests on building materials and structures — 
Part 22: Methods for determination of the fire resistance of non-load bearing elements of construction 
This standard has been superseded by the current BS EN 1634-1, but it has been in conjunction with BS 476-20 which describes the general principles for these retained based on legitimate need for the standards within non-EU markets. 

Scope 
This Part of BS 476 describes procedures for determining the fire resistance of non-load bearing elements of building construction when subjected to the heating and pressure conditions specified in BS 476-20.

Carry out the test in accordance with BS 476-20 and make any observations on the behaviour of the specimen, including the mode of failure in the event of collapse. 

The result shall be stated in terms of the elapsed time to the nearest minute, between the commencement of heating and the time of failure 

Samples shall be tested from both sides, i.e. two specimens

If testing is carried out from one side only, i.e. one specimen, the reason for this shall be clearly stated in the report. 

Determination of the fire resistance of glazed elements
Integrity.  Monitor the unexposed face of the specimen for evaluation of the integrity in accordance with clause 9 of BS 476-20:1987.

Insulation.  Measure the temperature rise of the unexposed face for evaluation of the insulation in accordance with clause 9 of BS 476-20:1987 for both the mean temperature rise and the maximum temperature rise.

Lateral deflection.  Whilst the specimen is not evaluated with respect to either the rate or extent of lateral deflection, monitor the glazing for deflection.

Irradiance.  Monitor the irradiance of the specimen by means of the radiometer in accordance with BS 476-20. 

Determination of the fire resistance of partitions 
Vertical glazed separating elements, partitions with less than 50 % glazing will be tested as partitions. 

Integrity.  Monitor the unexposed face of the specimen for evaluation of the integrity in accordance with clause 9 of BS 476-20:1987. 

Insulation.  Measure the temperature rise of the unexposed face for evaluation of the insulation in accordance with clause 9 of BS 476-20:1987 for both the mean temperature rise and the maximum temperature rise.

Deflection.  Monitor the maximum deflection of the specimen. 

Irradiance.  Monitor the irradiance of the unexposed face.

Determination of the fire resistance of fully insulated door-sets and shutter assemblies 
Integrity.  Monitor the temperature rise of the fixed frame components of the door or shutter assembly.

Insulation.  Measure the temperature rise of the unexposed face for evaluation of insulation in accordance with clause 9 of BS 476-20:1987, for both the mean temperature rise and the maximum temperature rise.

Monitor the temperature rise of the fixed frame components of the door or shutter assembly.

Lateral deflection.  Monitor the lateral deflection of the specimen. 

Determination of the fire resistance of partially insulated door-sets and shutter assemblies 
Integrity.  Until the criteria for insulation failure occurs, monitor the unexposed face of the specimen for evaluation of integrity in accordance with clause 9 of BS 476-20:1987.

Insulation. Measure the temperature rise of the unexposed face for evaluation of insulation in accordance with clause 9 of BS 476-20:1987, for both the mean temperature rise and the maximum temperature rise 

Monitor the temperature rise of the fixed frame components of the door or shutter assembly

Lateral deflection.  Monitor the lateral deflection of the specimen. 

Irradiance.  Monitor the irradiance by means of the radiometer described in BS 476-20

Determination of the fire resistance of uninsulated door-sets and shutter assemblies 
Integrity.  Monitor the unexposed face of the specimen for evaluation of integrity in accordance with clause 9 of BS 476-20:1987. 

Insulation.  Monitor the temperature rise of the unexposed face in accordance with clause 9 of BS 476-20:1987, for both the mean temperature rise and the maximum temperature rise.

Monitor the temperature rise of the fixed frame components of the door or shutter assembly.

Lateral deflection.  Monitor the lateral deflection of the specimen. 

Irradiance.  Monitor the irradiance by means of the radiometer described in BS 476-20.

For our full range of technical specifications please click on relevant headings below

Ballistic Technical Specifications
EN1063  Glass in Building - Security Glazing - Testing and Classification of Resistance Against Bullet Attack

UL752    Standard for Bullet-Resisting Equipment

BS5051  Bullet-resistant glazing - Part 1:  for interior use- Part 2: for Exterior use

NIJ 0108.01  US National Institute of Justice Standard-Test and Certification for Ballistic Resistant Materials

EN1522/3   Windows, doors, shutters and blinds - Bullet resistance - Requirements and classification /Test method

Blast Specifications
GSA-TS01:2003  Standard Test Method for Glazing and Window Systems Subject to Dynamic Overpressure Loadings

EN 13541   Glass in building - Security glazing - Testing and classification of resistance against explosion pressure 

EN 13123-2  Windows, doors and shutters - Explosion resistance - Requirements and classification

ISO 16933:2007 Glass in Building -- Explosion-Resistant Security Glazing -- Test & Classification for Arena Air-Blast Loading

Fire Specifications
UL 10C     Positive Fire Pressure Tests of Door Assemblies 

EN 1363-1    Fire resistance tests –Part 1: General Requirements

EN 1364-1     Fire resistance tests for non-load-bearing elements – Part 1: Walls

EN 1634-1   Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware 

Manual Attack  Specifications
EN 1627   Pedestrian door-sets, windows, curtain walling, grilles and shutters - Burglar resistance - Requirements and classification

LPS 1270  Intruder Resistant Security Glazing -  Requirements & Testing Procedures 

LPS 1175  Requirements and testing procedures for the LPCB certification and listing of intruder resistant building components, strongpoints, security enclosures and free-standing barriers

EN 356  Glass in building - Security glazing - Testing and classification of resistance against manual attack.

LPS 1175 and 1270 Tool Categories   Testing procedures for the LPCB approval

From Nanjing SMART (UKAS or CNAS)
Tel : (+86) 25 8658 3475   (+86) 400 603 6575
web :  www.fire-test.com   www.fire-test.cn
Email : info@fire-test.com
WeChat Official-"firetest" or "睿督防火测试"




版权所有 Copyright(C)2012-2015    南京睿督科技有限公司
地址:江苏省南京市建邺区江东中路118号德盈大厦1622 苏公网安备 32010502010098号  
电话:025-8658 3475   传真:025-8658 3457  网址:http://www.nff16-101.com/   邮箱:info@fire-test.com   备案号:苏ICP备10201999号