What is BS EN 13030:2001? EN13030防雨通风百叶窗测试评级标准
作者:admin    发布于:2022-05-19 10:16:27    文字:【】【】【

EN 13030 is a European standard which specifies a method for measuring the performance of louvres subject to simulated rain and wind pressures, both with and without air flow through the louvre under test. It provides a common basis on which to compare the performance of weather louvres of different designs, through the use of two defined performance criteria. 

Manufacturers wishing to test louvres against this standard typically supply a 1m x 1m sample for evaluation to a suitable test house, for example BSRIA, based in Bracknell, Berkshire. 

What performance criteria are louvres evaluated against?
EN 13030 states sample louvres should be evaluated for performance in terms of:

Resistance to ingress of simulated rain

How effective is a louvre at removing simulated rain (75 l/h) from an airstream when subjected to a constant wind speed (generally 13 m/s) and various air flow rates (0 m/s to 3.5 m/s in 0.5 m/s increments).

Class A – Excellent (99% effective and above)
Class B – Good (between 95% and 98.9% effective)
Class C – Fair (between 80% and 94.9% effective)
Class D – Poor (less than 80% effective)
Coefficient of entry/discharge

How much resistance does a louvre present to airflow? 

Class 1 – Excellent (Ce/Cd of between 0.4 and 1.0)
Class 2 – Good (Ce/Cd of between 0.3 and 0.399)
Class 3 – Fair (Ce/Cd of between 0.2 and 0.299)
Class 4 – Poor (Ce of 0.199 and below)
What does it mean to have a louvre tested against EN 13030?
The testing of a louvre against EN 13030 is not in itself a guarantee of performance, rather the louvre is graded against the two above performance criteria.

BS EN 13030:2001 建筑物通风-终端-遭受模拟雨的百叶窗的性能测试
BS EN 13030:2001 Ventilation for buildings-Terminals-Performance testing of louvrs subjected to simulated rain

AMCA Standard 500 Laboratory Methods of Testing Louvers for Rating

防风防雨性能极佳的百叶系统,其利用空气动力学截面原理达到通风防雨的效果,符合欧洲EN13030标准,该标准对应于美国AMCA500标准。

门窗相关测试认证标准参考
门窗CE认证协调标准 https://www.fire-test.cn/newsinfo/2119460.html
EN 12604:2017工业门机械性能测试/EN 13241工业门CE认证测试项目https://www.fire-test.cn/newsinfo/2279683.html
EN 356玻璃防盗性能测试(P1A,P2A,P3A,P4A,P5A,P6B,P7B,P8B) https://www.fire-test.cn/newsinfo/2387804.html
EN 1627:2011门窗防盗性能测试 https://www.firete.com/popular_standards/13647.html

更多关于EN 13030:2001百叶窗防风防雨性能测试,请咨询南京睿督公司
南京睿督全国免费咨询电话:400-603-6575 025-8658 3475
网址:www.hksmartps.com    www.fire-test.cn
邮箱:info@hksmartps.com


版权所有 Copyright(C)2012-2015    南京睿督科技有限公司
地址:江苏省南京市建邺区江东中路118号德盈大厦1622 苏公网安备 32010502010098号  
电话:025-8658 3475   传真:025-8658 3457  网址:http://www.nff16-101.com/   邮箱:info@fire-test.com   备案号:苏ICP备10201999号