CAN/ULC-S101加拿大建筑产品及构件耐火检测Fire Endurance Tests
作者:admin    发布于:2023-09-15 11:14:01    文字:【】【】【

许多应用于墙壁、隔断、天花板、柱子等场所的建筑产品需要保持一段时间的(如30分钟、60分钟、90分钟等)产品的完整性、隔热性的CAN/ULC-S101耐火标准要求。CAN/ULC-S101标准为加拿大建筑材料耐火测试标准。睿督已携手加拿大消防实验室Element机构为您提供专业权威的CAN/ULC-S101耐火测试报告,咨询电话:025-86583475。

加拿大耐火检测标准
CAN/ULC S101 Standard Methods of Fire Endurance Tests of Building Construction Materials
CAN/ULC S101 建筑材料及构件耐火测试标准

CAN/ULC-S101耐火测试方法
样品暴露下高温高压条件下,测试样品在规定时间内(30分钟、60分钟、90分钟、120分钟等)的承重量,完整性、隔热性。

CAN/ULC-S101耐火测试评估方面
耐火极限
隔热性和完整性对应承载能力
隔热性
完整性

Scope: These test methods are intended to evaluate the duration for which types of building elements contain a fire, retain their structural integrity, or exhibit both properties during a predetermined furnace test exposure. The test exposes a test specimen to a standard fire controlled to achieve specified temperatures throughout a specified time period. When required, usually for wall assemblies, the fire exposure is followed by the application of a specified standard fire hose stream exposure. The test provides a relative measure of the fire-test-response of comparable building elements under these fire exposure conditions.

Applicable Products: Assemblies of masonry units and composite assemblies of structural materials for buildings, including loadbearing and other walls and partitions, columns, girders, beams, slabs, and composite slab and beam assemblies for floors and roofs. Also applicable to other assemblies and structural units that constitute permanent integral parts of a finished building.

Test Procedure: The test specimen representative of the construction that the test is intended to assess, is assembled and installed abutting or on top of the appropriate test furnace. ?Test instrumentation will vary based on the nature of the sample under test and will usually include unexposed side thermocouples and/or thermocouples internal to the test assembly to monitor critical features. Depending on the testing requirements and sample type, external uniform loading may be applied to the sample for the duration of the test. The furnace is operated to expose the sample to the prescribed time temperature curve for the desired period of exposure, or until the applicable criteria have been exceeded. For most vertical assemblies, a standard fire hose water stream exposure is required and may be conducted on a duplicate sample.

End Result: Performance is defined as the period of resistance to standard exposure elapsing before the first critical point in behavior is observed. These critical points may include temperature rise, projection of flames or hot gases, failure to maintain applied load, etc. Results are reported in units in which field exposures can be judged and expressed. The test methods may be cited as the “Standard Fire Tests,” and the performance or exposure shall be expressed as "2-h",” "6-h",” “1/2-h,” etc. A comprehensive test report will be issued at the end of the conclusion of testing. If certification is chosen, the Listing Report and application Design Listings will be created and published following successful testing. Both the test report and Design Listings will include the achieved Fire Resistance Rating.

南京睿督公司咨询电话:025-8658 3475 025-8658 3465
网址:www.firete.com     www.fire-test.com 
邮箱:info@firete.com    info@fire-test.com
微信:firetesting  或    17714189018
...



版权所有 Copyright(C)2012-2015    南京睿督科技有限公司
地址:江苏省南京市建邺区江东中路118号德盈大厦1622 苏公网安备 32010502010098号  
电话:025-8658 3475   传真:025-8658 3457  网址:http://www.nff16-101.com/   邮箱:info@fire-test.com   备案号:苏ICP备10201999号